UPS5000-E-(30 kVA-120 kVA)-FM
User Manual
Item
Number of
iBOXs
Start address
for iBOX-NMS
communicati
on
iBOX number
of iBATs
Figure 4-32 Advanced Param.
Item
Current
source
Batt.
abnormal
BCB trip
Single batt.
group
number of
hall
Issue 02 (2020-11-10)
Description
The number of iBOXs
connected to UPS.
Specifies the communication
address when the
northbound device queries
iBOX data.
Specifies the number of
iBATs managed by the iBOX.
Description
Specifications of the Hall
effect sensor used to detect
iBOX current.
Specifies whether BCB trips
when batteries are abnormal.
Single batt. group number
of hall is equal to the
number of Hall effect sensors
at the positive or negative
terminal of a battery string
(Single batt. group number
of hall≥ 1).
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
0
0–6
0
0–124
0
0–300
Default Value
Value Range
Hall sensor
Hall sensor
200A
200A, Hall
sensor 600A
Disable
Disable,
Enable
1
1–8
114