UPS5000-E-(30 kVA-120 kVA)-FM
User Manual
After you press the EPO button, the EPO and No power supplied alarms are
displayed on the LCD.
5.10 Clearing the EPO State
Procedure
Step 1 Clear the EPO state. Ensure that the EPO button connected to the dry contact is
not in the EPO state.
Step 2 Clear the EPO alarm.
●
●
Step 3 Check that the EPO alarm is cleared by viewing active alarms. If the system bypass
input is normal, the UPS transfers to bypass mode.
●
●
Step 4 Start the inverter.
----End
5.11 Exporting Data
The following data can be exported:
●
●
●
●
●
●
Issue 02 (2020-11-10)
On the LCD
On the LCD, choose System Info > Alarms and tap Clear Faults. In the
displayed dialog box, tap Yes. The EPO alarm is cleared successfully.
On the WebUI
Choose Monitoring > UPS system > Running Control > Issued Order and
click Clear Fault. The EPO alarm is cleared successfully.
Viewing active alarms on the LCD
Choose System Info > Alarms > Active Alarms to check that the EPO alarm
is cleared.
Viewing active alarms on the WebUI
Choose Home > Active Alarm to check that the EPO alarm is cleared.
Historical Alarm
Active Alarms
Performance Data
Operation Log
E-Label
Fault Information
NO TE
This topic describes how to export historical alarms.