Connecting Communications Cables - Huawei UPS5000-E-600K-SC User Manual

Table of Contents

Advertisement

UPS5000-E-(600 kVA-800 kVA)
User Manual
Figure 3-67 Cable connection for an NC EPO switch
Figure 3-68 Cable connection for an NO EPO switch

3.2.9 Connecting Communications Cables

Procedure
Step 1 Connect the external network management device to the RS485 port.
3-10
Issue 02 (2016-01-20)
When the EPO switch is in the NC state, remove the jumper between EPO_NC and EPO_12V
before connection. When you turn off the EPO switch, EPO is triggered.
When the EPO switch is in the NO state, ensure that the jumper is connected between EPO_NC and
EPO_12V. When you turn on the EPO switch, EPO is triggered.
describe the RS485 pin definitions.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Installation
Figure 3-69
and
Table
100