User Manual
Table 3-3 Power cable terminal requirements
Port
Description
Mains input
Bypass
input
Battery
input
Output
PE
Table 3-4 Recommended upstream input and downstream output circuit breakers
UPS Capacity
30 kVA
Issue 02 (2020-11-10)
When the primary loads are non-linear loads, increase the cross-sectional
areas of the neutral wires 1.5–1.7 times.
The nominal battery discharge current refers to the current of forty 12 V
batteries at 480 V in standard configuration.
The maximum battery discharge current refers to the current when forty 12 V
batteries in standard configuration, that is, two hundred and forty 2 V battery
cells (1.67 V/cell), stop discharging.
When the mains input and bypass input share a power source, configure input
power cables as mains input power cables. In addition, cables listed in
3-2
apply only to the following conditions:
The cables are installed along the wall or on the floor (IEC-60364-5-52 C
standards).
The ambient temperature is 30°C.
The AC voltage loss is less than 3%, and the DC voltage loss is less than
1%. The recommended cable diameters in
through-current requirements. Users should evaluate the line voltage loss
based on the actual cable length. If the voltage loss exceeds the
requirements, increase the cable diameter properly.
The cables are single- or multi-core 90°C soft power cables with a copper
conductor.
Connection
Method
Crimped OT
terminals
Crimped OT
terminals
Crimped OT
terminals
Crimped OT
terminals
Crimped OT
terminals
Component
Mains input circuit breaker
Bypass input circuit breaker
Downstream output circuit
breaker
Copyright © Huawei Technologies Co., Ltd.
Bolt
Bolt Hole
Specifications
Diameter
M10
11 mm
M10
11 mm
M12
13 mm
M10
11 mm
M10
11 mm
3 Installation
Table 3-2
meet the basic
Bolt
Length
30 mm
30 mm
35 mm
30 mm
30 mm
a
Specifications
63 A/3P
63 A/3P
63 A/3P
Table
Torque
26 N·m
26 N·m
46 N·m
26 N·m
26 N·m
50