Capacity Test - Huawei UPS5000-E FM Series User Manual

Hide thumbs Also See for UPS5000-E FM Series:
Table of Contents

Advertisement

UPS5000-E-(30 kVA-120 kVA)-FM
User Manual
Step 2 Tap Start next to Shallow Dis. Test to start a shallow discharge test.
Figure 5-10 Starting a shallow discharge test
----End

5.6.1.3 Capacity Test

Context
Before a capacity test, ensure that:
● The UPS is working in normal mode; float charging or hibernation has lasted
● The UPS has generated no battery overtemperature, overvoltage, or overcurrent
● The mains, batteries, charger, and discharger are normal. No overload alarm is
Procedure
Step 1 On the home screen of the LCD, choose System Info > Maintenance > Battery
Maint.
Issue 02 (2020-11-10)
NO TE
When the battery test is complete, the test data is used as common test data. Record the
data obtained from the latest five tests.
The shallow discharge test automatically stops in any of the following cases:
● The battery discharge capacity reaches the specified value (10%–50%, 20% by default).
● The discharge voltage reaches the warning threshold (calculated in real time).
● The load ratio fluctuation exceeds 10%.
● An alarm is generated.
NO TICE
for 2 hours after the state of charge (SOC) reaches 100%; and the load ratio
fluctuation is less than 10%.
alarm. No generator is connected to the UPS.
generated.
Copyright © Huawei Technologies Co., Ltd.
5 Operations
153

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ups5000-e-120k-fmUps5000-e-30k-fm

Table of Contents