NETWORK SCREENS
Modbus Network Settings
For MS8350 and MS8650
Modbus Network Settings
Modbus network screen shows when Modbus is selected in wired protocol parameter.
Figure 19: Modbus Network Setting Display.
1 /1 Mo d bu s Netw ork
C OM a d dress
N et wor k un it s
B aud r at e
P ar ity
Table 7: Modbus Network Parameter Details.
Configuration Parameters Default Value
Communication Address
Default Value: 254
Network Units (Measurement Units)
Default Value: SI
Baud rate (Modbus Baud Rate)
Default Value: 19200
Parity
Default Value: Even
24
254
SI
19200
No n e
Valid address range is set at 1 to 247 and each Modbus device must have a unique ad-
dress. Other values not recommended for Modbus.
Default value of 254 disables Modbus communication for the Controller.
Range: 0 to 254
Network units transmitted over the Modbus network.
Use the Temperature scale parameter to change the display units locally on the Controller.
Imperial: network units shown as Imperial units.
SI: network units shown as International Metric units.
Choices: Imperial or SI
Automatically detects Modbus baud rate.
Choices: 57600, 38400, 19200, 9600, and 4800
Determines how the parity bit of the character's data frame is set to detect any errors in the
sent / receives frame.
Choices: None, Odd and Even