CONFIGURATION SCREENS
MS8650 Configuration 2 / 11
For MS8650 Only
MS8650 Configuration 2 / 11
Figure 34: MS8650 Configuration 2 / 11 Display.
2/ 11 C o n f i g u r a t io n
F an co n t . h e a t
F an d e la y
S ta n d b y m o d e
S ta n d b y d if f .
P o we r - u p d e la y
O ccu p a n c y s r c
Table 27: MS8650 Configuration 2 / 11 Parameter Details.
Configuration Parameters Default Value
Fan Cont. Heat (Fan Control in Heating
Mode)
Default Value: On
Fan Delay
Default Value: On
Standby Mode (Standby Mode
Configuration)
Default Value: Absolute
Standby Diff. (Standby Temperature
Differential)
Default Value: 4°F (2°C)
Power-up Delay
Default Value: 10 seconds
Occupancy Src (Occupancy Source)
Default Value: Motion
44
O n
O n
A b s o l u t e
2 .0 ° F
1 0 S e c .
M o t io n
On: Room Controller always controls the fan (terminal G). Valid for On or Auto fan mode.
Off: Fan (terminal G), when heating stages (terminals W1 and W2) are solicited, will not be ener-
gized. The fan is controlled by the equipment fan limit control. Valid only for Auto fan mode. On
fan mode leaves the fan always on.
For multi-stage models, fan control applies to W1 and W2.
Choices: On or Off
On: fan mode will leave the fan always on and extends fan operation by 60 seconds after the call
for heating or cooling ends. Valid only for Auto fan mode.
Off: fan delay not operational
Choices: On or Off
Standby setpoints used for control.
Absolute: Standby entered values are used for standby mode.
Offset: Occupied setpoints +/- Standby diff. used for standby mode.
Choices: Absolute or Offset
When Standby mode is set to "offset", standby setpoints are calculated as follows:
Standby cool: Cool setpoint + Standby diff.
Standby heat: Heat setpoint - Standby diff.
Range: 1 to 5°F (0.5 to 2.5°C)
On initial power up of the Room Controller there is a delay before any operation is authorized
(fan, cooling or heating). This can be used to sequence the start up of multiple Room Controllers
in one location.
Range: 10 to 120 seconds
Motion: Occupancy status is received from a motion sensor from a wired, wireless or local PIR sensor.
Schedule: Occupancy status is determined by the schedule
Choices: Motion or Schedule
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp.
Significance and Adjustments

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Multisite ms8350Multisite ms8650

Table of Contents