CONFIGURATION SCREENS
MS8350 Configuration 8 / 9
For MS8350 Only
MS8350 Configuration 8 / 9
Figure 31: MS8350 Configuration 8 / 9 Display.
8/9 Co nfig u ratio n
Calib. temp .
Calib. humid .
RH sensor
Table 23: MS8350 Configuration 8 / 9 Parameter Details.
Configuration Parameters Default Value
Calib. Temp. (Calibration Room
Temperature Sensor)
Default Value: 0°F
Calib. Humid. (Calibrate Humidity Sensor)
Default Value: 0.0%RHF
RH Sensor (Relative Humidity Sensor)
Default Value: Internal
40
0.0 ° F
0.0 %RH
N o ne
Room temperature sensor calibration. Offset can be added or subtracted to actual dis-
played room temperature.
Range: ± 5.0°F (± 2.5°C)
Offset that can be added or subtracted to actual displayed humidity.
Range: ± 15.0% RH
Sets the source of the indoor room humidity. This parameter allows the user to designate
either the Room Controller (only models supporting humidity) or any of the bound wireless
devices that support humidity to act as the source for the room humidity.
Internal: Sets the Room Controller as the source for the room humidity.
WL 1 to WL 10: Sets the selected wireless ZigBee PRO device as the source for the room
humidity. Only one device can be selected.
Choices: None, Internal, WL1 to WL10
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp.
Significance and Adjustments

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Multisite ms8350Multisite ms8650

Table of Contents