NETWORK SCREENS

ZigBee Network 1 / 2

For MS8350 and MS8650
ZigBee Network 1 / 2
When setting up a ZigBee network to bind with multiple devices, there must first be a Coordi-
nator to manage the initial binding between the Router and the end devices. After successful
binding, the Router becomes the parent to the end devices.
Before binding any ZigBee devices, the network must first be created by the Coordinator..
Table 4: ZigBee Network 1 / 2 Parameter Details.
Configuration Parameters
Default Value
Controller networking address. For wireless models, the use of the COM address is not mandatory. The COM
address is an optional way to identify a device on the network and is recommended if used with an MPM. It is
COM Address
Mandatory for BACnet.
Default Value: 254
Range: 0 to 254
Sets device to act as Router or Coordinator in a network.
Coordinator: Creates the network and manages the binding of wireless devices.
Node Type
Router: Joins a network created by a coordinator (permit join must be set to "ON").
Default: Router
Choices: Coordinator or Router
Personal Area Network Identification that links specific Controllers to specific ZigBee coordinators. For every
Controller reporting to a coordinator, set the SAME PAN ID value both on the coordinator and the Controller.
Pan ID (ZigBee Pan ID)
• The default value of 0 is NOT a valid PAN ID.
Default Value: 0
• For Controllers running Firmware version 1.3 and earlier, the PAN ID must be set to 501-1000 for the Controller
to act as a coordinator.
Range: 1 to 32767
The frequency or channel on which the ZigBee network transmits and receives data. The channel of the Coordi-
nator must match that of the routers to exchange data.
Channel (ZigBee
The default value of 10 is NOT a valid channel. The valid range of available channel is from 11 to 25.
Channel)
Default Value: 10
Using channels 15 and 25 is recommended.
Range: 10 to 25
Shows the current status of the ZigBee network.
No NWK: ZigBee configured but no network joined
Network Status (ZigBee
Network Status) Read
Joined: ZigBee network joined
Only
Online: Communicating (Exchanging data)
Display Readings: No NWK, Joined, Online
Changing this value to "Off" on the Coordinator prevents any new ZigBee devices from joining the network.
Permit Join
Permit join can be On/Off when the Controller is a Coordinator, however the parameter is read only when the
Default Value: On
Controller is a router. If not set to off manually the Permit join will stay On for 3 hours.
Choices: On or Off
20
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp.
Figure 15: ZigBee Network 1 / 2 Display.
Significance and Adjustments
1/2 ZigBee Network
COM address
254
Node type
Router
PAN ID
25
Channel
15
Network status
No NWK
Permit join
Off