Table 36: MS8650 Configuration 7 / 11 Parameter Details, continued.
Configuration Parameters Default Value
Min Fresh Air (Minimum Fresh Air)
Default Value: 0 CFM
Max Fresh Air (Maximum Fresh Air)
Default Value: 0 CFM
Min CO
(Minimum CO
)
2
2
Default Value: 800 ppm
Max CO
(Maximum CO
)
2
2
Default Value: 1200 ppm
Minimum fresh air required (minimum outside airflow setpoint). Effective only in Occupied,
Standby or Override mode and Fan status is ON. If FA Range is set to value other than 0
CFM, the fresh air damper position control will be based on the Min/Max CO
Fresh Air values.
If Room Controller is in Unoccupied mode and/or the Fan is Off, the damper position goes
to 0%.
Range: 0 to 20,000 CFM (±10 increments). The value set cannot exceed the value of FA
Range parameter.
Maximum fresh air allowed (maximum outside airflow setpoint). Effective only in Occupied,
Standby or Override mode and Fan status is ON. If FA Range is set to value other than 0
CFM, the fresh air damper position control will be based on the Min/Max CO
Fresh Air values.
Range: 0 to 20,000 CFM (±10 increments). The value set cannot exceed the value of FA
Range parameter.
Minimum CO
level setpoint. Effective only in Occupied, Standby or Override mode and
2
Fan status is ON. The Outside Air damper modulates to maintain the CO
"Min CO
" and "Max CO
2
Outside Air damper position goes to 0%.
Range: 0 to 2,000 ppm
Maximum CO
level setpoint. Effective only in Occupied, Standby or Override mode and
2
Fan status is ON. The Outside Air damper modulates to maintain the CO
"Min CO
" and "Max CO
2
Range: 0 to 2,000 ppm
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp.
CONFIGURATION SCREENS
MS8650 Configuration 7 / 11
Significance and Adjustments
". If the Controller is in Unoccupied mode and/or the Fan is Off,
2
".
2
For MS8650 Only
and Min/Max
2
and Min/Max
2
level between
2
level between
2