CONFIGURATION SCREENS
MS8650 Configuration 4 / 11
For MS8650 Only
Table 31: MS8650 Configuration 4 / 11 Parameter Details, continued.
Configuration Parameters Default Value
Anti Short Cycle (Anti Short Cycle
Time)
Default Value: 2 minutes
Min. Sup. Heat (Minimum Supply
Heat)
Default Value: 64°F (18°C)
48
Minimum On time and minimum Off time of operation time for stages.
Anti-short cycling can be set to 0 minutes for equipment that possess their own anti cycling timer.
Do not use this value unless the equipment is equipped with an internal timer. Failure to do so can
damage the equipment.
Range: 0 to 5 minutes
Controls the modulating heating output to maintain the supply air temperature setpoint (min. sup.
heat).
Apply if "Heat Stages" parameter is set to 0 (Analog Heat on UO11). In Occupied or Override
mode, the output will modulate to maintain a minimum Supply Air temperature. Conditional to
SAT sensor installed, System Mode = Heat or Auto and OAT < SH Lockout.
Range: 50°F to 72°F (10°C to 22°C)