LG MultiSITE MS8000 Series User Manual page 34

Room controllers
Hide thumbs Also See for MultiSITE MS8000 Series:
Table of Contents

Advertisement

CONFIGURATION SCREENS
MS8350 Configuration 4 / 9
For MS8350 Only
MS8350 Configuration 4 / 9
Figure 27: MS8350 Configuration 4 / 9 Display.
4/9 Configuration
Standby time
Unocc. time
Temp. occ. time
Deh. hysteresis
Deh. max. cool
Deh. lockout
Table 17: MS8350 Configuration 4 / 9 Parameter Details.
Configuration Parameters Default Value
Standby Time
Default: 0.5 hours
Unocc. Time (Unoccupied Time)
Default: 0.0 hours
Temp. Occ. Time (Temporary
Occupancy Time)
Default value: 2 hours
Deh. hysteresis (Humidity Control
Hysteresis)
Default Value: 5 % RH
Deh. Max. Cool. (Dehumidification
Maximum Cooling Limit)
Default value: 100 %
Deh. Lockout (Dehumidification
Lockout)
Default value: Disabled
34
0.5 hrs
0.0 hrs
2.0 hrs
5 %RH
100%
Enabled
Time between the moment where the PIR cover detects last movement in the area, and the time
which the Room Controller stand-by setpoints become active.
This parameter is not active when the "Door" function is used (wired or wireless).
Range: 0.5 to 24.0 hours (0.5 hour increments)
Time between the moment where the Room Controller toggles to stand-by mode, and the time
which the Room Controller unoccupied mode and setpoints become active.
Default value of 0.0 hours disables the unoccupied timer. This prevents the Room Controller from
being able to switch from stand-by mode to unoccupied mode when PIR functions are used.
Range: 0.0 to 24.0 hours (0.5 hour increments)
The time the Room Controller stays in override mode before reverting back to unoccupied
mode. When the Room Controller is in unoccupied mode, pressing the on-screen Override icon
or closing the contact on UI17, configured as "Remote Override", sets the Room Controller to
Override mode for defined time period, and uses the Occupied Cooling and Heating setpoints.
Range: 0.0 to 24.0 hours
Used only if dehumidification sequence is enabled.
Range: 2 to 20% RH
Maximum cooling valve position when dehumidification is enabled. This can be used to balance
smaller reheat loads installed in regards to the capacity of the cooling coil.
Range: 20 to 100%
Enables or disables dehumidification based on central network requirements from the BAS front end.
Enabled: Dehumidification Authorized
Disabled: Dehumidification Not Authorized
Choices: Enabled or Disabled
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp.