MS8650 Configuration 1 / 11
Table 26: MS8650 Configuration 1 / 11 Parameter Details, continued.
Configuration Parameters Default Value
UI19 Config (Universal Input Configuration
No. 3)
Default Value: None
Smart Recovery (Enable Smart Recovery)
Default Value: Off
Setpoint Func. (Setpoint Function)
Default Value: Dual SP
Mode Button
Default Value: Normal
This input is used for a wired CO
None: No function associated with input, however input can be used for remote network
monitoring.
CO
: Using the CO
2
Outside Air damper (Econo) will modulate between "Econo min pos" to "Econo max pos"
following the "Min CO
Choices: None or CO
Off: No smart recovery. The occupied schedule time is the time at which the system will
restart.
On: Smart recovery active. The occupied schedule time is the time at which the desired
occupied temperature will be attained. The Room Controller automatically optimizes the
equipment start time. In any case, the latest a system will restart is 10 minutes prior to the
occupied period time.
Smart recovery is automatically disabled if BI16 is configured to remote NSB.
Choices: Off or On
Local setpoint settings to set the local setpoint interface for the User.
Dual SP: "Minimum" Deadband, Heat and Cool Setpoints can be adjusted independently.
Attach SP: "Fixed" Deadband, Heat and Cool setpoints always follow each other, sepa-
rated by Deadband value (acts like a single setpoint).
Choices: Dual SP or Attach SP
Changes the behavior of the system mode button functionality and hides/shows tempera-
ture setpoints on main screen.
Normal: System mode button switches between "Off", "Auto", "Cool" and "Heat". Also
displays temperature Setpoints on main screen.
Off-Auto: System mode button switches between "Off" and "Auto". Hides temperature
Setpoints on main screen.
Setting "Mode button" to "Off-Auto" forces the "Setpoint func" parameter to "Attach SP".
Choices: Normal or Off-Auto
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp.
CONFIGURATION SCREENS
MS8650 Configuration 1 / 11
Significance and Adjustments
sensor.
2
level measured by a wired CO
2
" and "Max CO
" setpoints.
2
2
2
For MS8650 Only
sensor (0~2,000 ppm = 0~10 Vdc), the
2
43