MS8650 Configuration 5 / 11
Figure 37: MS8650 Configuration 5 / 11 Display.
5/11 Co nfigurati on
P ro p. b an d
Heat s tag es
C o o l sta ge s
Eco n o. c on fi g
C h an geo ver SP
M ech . co o ling
Table 32: MS8650 Configuration 5 / 11 Parameter Details.
Configuration Parameters Default Value
Prop. Band (Proportional Band
Setting)
Default Value: 3
Heat Stages (Number of Heating
Stages)
Default Value: 2 stages
3.0
2
2
Off
55 ° F
Off
Adjusts proportional band used by Room Controller PI control loop.
Default value of 3 gives satisfactory operation in most normal installation cases. The use of a superior
proportional band different than the factory value is normally warranted in applications where Room
Controller location is problematic and leads to unwanted cycling of the unit. A typical example is a wall
mounted Room Controller installed between return and supply air feeds and is directly influenced by
the supply air stream of unit.
Range: 3 to 10
Value
3
4
5
6
7
8
9
10
Sets number of Heating Stages applicable to 2 stage models only.
0 Stages: Only (UO11) modulating 0-10 Vdc output is used for Heating. W1 and W2 are dis-
abled.
1 Stage: Only W1 (BO8) terminal is used. W2 is disabled.
2 Stages: Both W1 (BO8) and W2 (UO9) terminals are used in sequence.
Choices: 0, 1 or 2 stages
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp.
CONFIGURATION SCREENS
MS8650 Configuration 5 / 11
Significance and Adjustments
Effective Proportional Band
Fahrenheit
3
4
5
6
7
8
9
10
For MS8650 Only
Celsius
1.2
1.7
2.2
2.8
3.3
3.9
5.0
5.6
49