MS8650 Setpoints 1 / 2

Figure 46: MS8650 Setpoints 1 / 2 Display.
1 / 2 Setp oin ts
Un o c c . c oo l
S ta nd b y c o o l
Oc c . c o ol
Oc c . h e a t
S ta nd b y he at
Un o c c . h e a t
Table 44: MS8650 Setpoints 1 / 2 Parameter Details.
Configuration Parameters Default Value
Unocc. Cool (Unoccupied Cool Setpoint)
Default Value: 80°F (27°C)
Standby Cool (Standby Cool Setpoint)
Default Value: 78°F (25.5°C)
Occ. Cool (Occupied Cool Setpoint)
Default Value: 75°F (24°C)
Occ. Heat (Occupied Heat Setpoint)
Default Value: 72°F (22°C)
Standby Heat (Standby Heat Setpoint)
Default Value: 69°F (20.5°C)
Unocc. Heat (Unoccupied Heat Setpoint)
Default Value: 62°F (17°C)
7 9 .7 °F
77 .9 °F
75 .2 °F
71 .6 °F
68 .9 °F
61 .7 °F
Cooling Temperature setpoint used by the Room Controller when in Unoccupied mode.
Range: 54 to 100°F (12.0 to 37.5°C)
Cooling Temperature setpoint used by the Room Controller when in Standby mode.
Range: 54 to 100°F (12.0 to 37.5°C)
Cooling Temperature setpoint used by the Room Controller when in Occupied or Override
mode.
Range: 54 to 100°F (12.0 to 37.5°C)
Heating Temperature setpoint used by the Room Controller when in Occupied mode.
Range: 40 to 90°F (4.5 to 32.0°C)
Heating Temperature setpoint used by the Room Controller when in Standby mode.
Range: 40 to 90°F (4.5 to 32.0°C)
Heating Temperature setpoint used by the Room Controller when in Unoccupied or Over-
ride mode.
Range: 40 to 90°F (4.5 to 32.0°C)
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp.
SETPOINTS SCREENS
MS8650 Setpoints 1 / 2
Significance and Adjustments
For MS8650 Only
61

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Multisite ms8350Multisite ms8650

Table of Contents