FRONT CONTROL PANEL INTERFACE

Relay messages

Target messages

3–6
Courtesy of NationalSwitchgear.com
To clarify this ambiguity, the BKR CONNECTED function under SETPOINTS/S2 SYSTEM
SETUP/S2 BREAKER should be programmed to an additional contact input. When this
additional input is closed, a single 52a or 52b contact will show both breaker states.
When the breaker is racked out, this additional breaker connected input should be
open. In this case, both breaker status indicators will be off.
MAINTENANCE: Amber
This LED may indicate both breaker or relay maintenance depending on the
programmed maintenance elements. The LED will turn on upon operation of a
maintenance element.
Target messages are automatically displayed for any active condition on the relay such as
pickups, trips, or alarms.
The relay displays the most recent event first, and after 5 seconds will start rolling up the
other target messages until the conditions clear and/or the RESET command is initiated.
The Target Messages can be reviewed by pressing either the MESSAGE UP or MESSAGE
DOWN key. If a RESET command is not performed but any of the other faceplate
pushbuttons is pressed, the display will not show the target messages unless the user
navigates to
ACTUAL VALUES > A4 TARGET MESSAGES
target messages have not been cleared before the user presses a pushbutton different
from "RESET", they will reappear on the screen after the time specified under the
SETPOINTS > S1 RELAY SETUP > S1 FRONT PANEL > MESSAGE TIMEOUT
timing out from the last pressed pushbutton. The following shows the format of a typical
Target Message:
Figure 4: Typical target message
Figure 5: Example of a Phase IOC1 Operation - Phase A Function: Trip
Cause <Function>
The first line contains information of the cause of operation (the name of the operated
element), and the element function.
State: Operate
This line from the display shows the state of the element: Pickup, Operated, Alarm.
Phase: A
The last line from the display shows the phase that picked up or operated.
, where they can be reviewed. If the
A4 TARGET MESSAGES
Cause <function>
State: Operate
Phase:
A4 TARGET MESSAGES
Ph IOC1 Trip
State: Operate
Phase:A
345 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 3: INTERFACES
setting, that will start