Output Relay 2 (F4) Programmed As Close - GE 850 Instruction Manual

Feeder protection system
Hide thumbs Also See for 850:
Table of Contents

Advertisement

OUTPUTS
Output Relay 2 (F4)
programmed as Close
NOTE:
NOTE
NOTE: For
NOTE
5–100
Output Relay 2 (F4) is labeled CLOSE/AUX on the wiring diagram. As suggested by that
name, it can be used as a Close relay or an Auxiliary relay. This selection is made at
Setpoints > System > Breakers (Contactor) > Breakers 1 (Contactor 1) > Close Relay Select
the selected value of the Close Relay Select setting is Off, Output Relay 2 functions as an
Auxiliary relay. If the selected value is Relay 2, Output Relay 2 functions as a Close relay.
The default value is Off. The description below applies to both Relay 2 "Close" functionality.
For the Relay 2 "auxiliary" functionality; see the
in the next section.
Path:
Setpoints > Outputs > Output Relays > Aux Relay 2 (Close)
The output relays selected under the Breaker menu for breaker closing are excluded from
the list of outputs for selection under the menus of all elements providing such output
relay selection.
If Aux Relay 2 is selected for Breaker Close or Contactor Close, the relay name from the
Output Relays menu changes to "Close". If Aux Relay 2 is not selected, the name reverts to
"Aux Relay 2".
CHAPTER 5: DEVICE, SYSTEM, INPUT AND OUTPUT SETPOINTS
Figure 5-37:Auxiliary Relays generic logic
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL