Digital Interface - E+E Elektronik EE741 Series User Manual

Inline flow sensor for compressed air and gases
Hide thumbs Also See for EE741 Series:
Table of Contents

Advertisement

The minimum time between two pulses is 2 s.
OUT 2
≥ 2 s
1/3
min. 2/3
Fig. 5
Pulse-pause ratio
The pulse duration and the pulse value can be calculated with following MIN/MAX-Formula:
Calculating the min. "pulse value" or the max. "pulse duration":
IMPW_MIN = NORMV_MAX [m³/h] * IMPL [s] / 1200
IMPL_MAX = IMPW [m³] * 1200 / NORMV_MAX [m³/h]
IMPW
IMPL
IMPW_MIN
IMPL_MAX
NORMV_MAX max. expected standard volume flow [m³/h]
The totalized consumption is stored every minute and is retained even if the supply voltage is
interrupted.
The totalized consumption can be shown on the display. A reset of the consumption meter can be
performed via the display menu or the EE-PCS Product Configurator Software.
3.2.3

Digital Interface

The EE741 is available in three different digital interface versions, with Modbus RTU, M-Bus
or IO-Link interface. The Modbus RTU and M-Bus interface parameters can be accessed and
changed with the help of the EE-PCS Product Configurator Software.
User Manual EE741 Inline Flow Sensor for Compressed Air and Gases
pulse value [m³]
pulse duration [s]
min. value for pulse value [m³]
max. pulse duration [s]