Led Indication; Digital Settings - E+E Elektronik EE210 User Manual

Humidity and temperature sensor for demanding climate control applications
Hide thumbs Also See for EE210:
Table of Contents

Advertisement

LED INDICATION

Green LED
Information during normal operation
on
= everything OK
flashing = the main board does not recognize the
measurement electronics inside the RH probe
off
= no power supply or main board failure
DISPLAY
Factory Setup:
The display shows the two parameters selected for output 1 and output 2 (according to ordering
code). For digital output versions the display shows RH and T.
User Setup:
The user can change the display layout to 1, 2 or 3 lines and select the
parameters to be displayed by using EE-PCS Product Configuration Software (free download from
www.epluse.com/configurator) and the optional USB configuration adapter (not included in the
scope of supply).
Important: The EE210-M1xA6 (4...20 mA, 2-wire version) with display operates correctly only if
both outputs are connected.
SELECTION OUTPUT SIGNAL U/I
The factory setup of the output signal and scaling corresponds to the type number as ordered.
The output signal (voltage or current 3-wire) can be selected with the DIP switch on the main electronics board (see picture PCB
EE210-M1xA2/3/5). This does not impact on the scaling of the outputs, which can be changed using USB configuration adapter and
the EE-PCS.
Examples
Factory setup: voltage output 0 - 5 V or 0 - 10 V corresponds to 0...100%RH.
After switching from U to I: current output 0...20 mA corresponds to 0...100%RH.
A change of the current output range for instance to 4 - 20 mA (3-wire) can be made subsequently with the USB configuration adapter
and EE-PCS.
Factory setup: current output 0 - 20 mA corresponds to -10...50 °C.
After switching from I to U: voltage output 0 - 10 V corresponds to -10...50 °C.
A change of the voltage output range for instance to 0 - 5 V can be made subsequently with the USB configuration adapter and
EE-PCS.

DIGITAL SETTINGS

HARDWARE BUS TERMINATION
If required, the bus termination shall be realized with 120 Ohm resistor, jumper on the board.
• Jumper mounted
• Jumper not mounted = bus not terminated
ADDRESS SWITCH
Address Switch
0 0 0 0 0 0 0 0
Address Switch
1 1 0 1 0 0 0 0
4
= bus terminated
Address setting via EE-PCS Product Configuration Software
0
All DIP switches at position 0 → address has to be set via
1
Product Configuration Software
Factory setting: 242 (permitted values: 1...247).
Example: Slave address is set via configuration software.
Address setting via DIP switch
0
Setting the DIP switches to any other address than 0, overrules the
1
slave address set via configuration software (permitted values: 1...247).
Example: Slave address set to 11 (= 0000 1011 binary).
Blue LED
Information during setup with the optional USB
configuration adapter HA011066 and the EE-PCS
Product Configuration Software
on
= USB stick connected to PC, no communication
with EE-PCS
flashing = communication in progress with EE-PCS
off
= USB stick not connected to PC