Parameterisation
Attribute no. Access
2
Get
3
Get/Set
4
Get/Set
5
Get/Set
6
Get/Set
7
Get/Set
8
Get/Set
9
Get/Set
Festo — CPX-E-EP — 2020-01a
Description
Status of diagnostic memory (bit 0, 1)
0 = Recording active
1 = Recording inactive
Clear_trace1, access via EDS
Clear_trace2, access via explicit mes-
saging; confirmation of execution by
resetting (0) the attribute value
Entries saved retentively with Power On
(bit 0)
0 = active (default)
1 = inactive
Run/stop filter 1 (bit 1)
0 = Save the first 40 entries, stop after 40
entries
1 = Save the last 40 entries, overwrite
existing entries (default)
Run/stop filter 2 (bit 0 
0 = Run/stop filter 2 inactive (default)
1 = Record up to the defined error num-
ber (FN)
2 = Record up to the defined FN + module
number (MN)
3 = Record up to the defined FN + MN +
channel number (KN)
4 = Record from the defined FN
5 = Record from the defined FN + MN
6 = record from the defined FN + MN + KN
7 = Reserved
Error end filter (bit 3)
0 =Filter inactive, record running errors
(end of error) (default)
1 = Filter active, do not record running
errors (end of error)
Error number filter (bit 4, 5)
0 = Filter inactive (default)
1 = Record only defined error numbers
2 = Do not record defined error numbers
3 = Reserved
Type
BYTE
BYTE
BYTE
BYTE
BYTE
 2)
BYTE
...
BYTE
BYTE
Function
number
3483 (bit 0,
1)
3480 bit 0)
3480 bit 1)
3484 (bit
 2)
...
3484 (bit 3)
3484 (bit 4,
5)
37