Parameterisation
Ethernet Link Object
–
Object class: 246
d
–
Instances: 3
General information and status information as well as advanced settings for the Ethernet interfaces.
Instance 1 corresponds to Ethernet port X1 and instance 2 corresponds to Ethernet port X2.
Attribute no.
Access
1
Get
2
Get
3
Get
4
Get
Festo — CPX-E-EP — 2020-01a
Description
Interface speed (in Mbps)
Interface flags
Bit 0: Link status
0 = inactive link
1 = active link
Bit 1: Halfduplex/Fullduplex
0 = half duplex
1 = full duplex
Bit 2
4: Negotiation status
...
0 = Auto-negotiation in progress
1 = Auto-negotiation and speed detection failed
2 = Auto-negotiation failed but detected speed
3 = Successfully negotiated speed and duplex
4 = Auto-negotiation not attempted
Bit 5: Manual setting requires reset
0 = No local hardware fault
1 = Local hardware fault detected
Bit 6: Local hardware fault
Physical address (MAC layer address)
Interface counters
–
In octets
–
In Ucast packets
–
In NUcast packets
–
In discards
–
In errors
–
In unknown protos
–
Out octets
–
Out Ucast packets
–
Out NUcast packets
–
Out discards
–
Out errors
Type
UDINT
DWORD
ARRAY of
UINT[6]
STRUCT of
UDINT
25