Function
2.1.7
Control Elements
Rotary/DIL switches
Tab. 5 Rotary/DIL Switches
In the case of invalid values, the IP parameters are reset to dynamic addressing (DHCP). For switch
positions 0 ... 255, the protocols EtherNet/IP and Modbus TCP can be used in parallel. The rights to
control the outputs are assigned to the protocol that sends outputs first.
DIL switch
DIL 1:
OFF
DIL 2:
OFF
DIL 1:
OFF
DIL 2:
ON
DIL 1:
ON
DIL 2:
OFF
10
Function
The 3 rotary switches are used to set the 4th octet of the IP address
(192.168.1.XXX).
Possible Settings:
–
0 = Dynamic addressing via DHCP/BOOTP
–
1
255 = permissible address range
...
Valid Values:
–
EtherNet/IP: 300
...
–
Modbus TCP: 600
–
Factory setting: 900
In the case of invalid values, the IP parameters are reset to dynamic
addressing (DHCP).
The diagnostic mode is set using the DIL switches
Function
No diagnostics
1)
Status bits activated
I/O diagnostic interface activated
555 (IP address = value
855 (IP address = value
...
300)
–
600)
–
Tab. 6 DIL Switch.
è
Festo — CPX-E-EP — 2020-01a