Parameterisation
3.2.5
Cycle time (Port 1 ... 4)
The "Cycle time" parameter defines the cycle time (low/high) set by the IO-Link master.
The setting can be made separately for each IO-Link interface (port).
The value becomes effective at the start of the IO-Link connection by setting the "Operating mode"
parameter to "IO-Link" (è Tab. 22). Changes during IO-Link operation are not made until the connec-
tion has been deactivated and then reactivated again.
Parameter – cycle time
Setting
Cycle time (Port 1)
Low
High
Cycle time port 2
Low
High
Cycle time port 3
Low
High
Cycle time port 4
Low
High
1) Function number (è Description of automation system CPX-E); m = module number (counted from left to right, starting from 0)
2) In case of a setting of 0, the minimum supported cycle time of the IO-Link device is used.
Tab. 20
20
Comments
16 Bit (in 100 µs unit)
2)
Default = 0
2)
16 bit (in 100 µs unit)
Default = 0
2)
16 bit (in 100 µs unit)
Default = 0
2)
16 bit (in 100 µs unit)
Default = 0
2)
16 bit (in 100 µs unit)
Default = 0
16 bit (in 100 µs unit)
2)
Default = 0
2)
16 bit (in 100 µs unit)
Default = 0
2)
16 bit (in 100 µs unit)
Default = 0
Selection via parameter
F no.
Bit
1)
4828 +
7
6
5
64m
+ 8
+ 9
+ 12
+ 13
+ 16
+ 17
+ 20
+ 21
Festo — CPX-E-4IOL-... — 2020-01a
4
3
2
1
0