Cc-Link Ie Tsn; Outline - Mitsubishi Electric FR-E800 Instruction Manual (Communication

Hide thumbs Also See for FR-E800:
Table of Contents

Advertisement

2.5

CC-Link IE TSN

2.5.1

Outline

Data can be transmitted to IT systems while performing real-time cyclic communication control.
Some functions are not supported depending on the date of manufacture of the inverter. For details of specification changes,
refer to
page
220.
 CC-Link IE TSN authentication classes
• Devices (nodes) and switches on the CC-Link IE TSN network are classified into different authentication classes according
to their functionality and performance. There are two authentication classes: A and B. For details of the authentication class
of each product, check the information on the web site of the CC-Link Partner Association, or refer to catalogs and manuals
of each product. Different functions and system configurations are available depending on the authentication class of the
devices to be used. For example, use authentication class B devices to construct a high-speed motion control system. For
details of system construction such as mixing devices of both class A and class B, check the manuals of the applicable
master device.
 Communication specifications
The communication specification varies depending on the specification of the master.
Item
Transmission speed
Minimum synchronization cycle
Authentication class
Communication method
Synchronization function
Maximum number of connected units
Maximum number of branches
Connection cable
Topology
Node type
Maximum cyclic size (of
one node)
*1
Ring topology will be supported later.
NOTE
• To use the CC-Link IE TSN, do not install the FR-A8NC to the inverter. (Installing the FR-A8NC E kit disables CC-Link IE TSN.)
18
2. Ethernet Communication
2.5 CC-Link IE TSN
100 Mbps (10 Mbps is not supported.)
5000.00 μs
Authentication class A
Time sharing method
Conforms to IEEE 1588v2
121 units (sum of master and slave stations)
No upper limit on the same Ethernet network
Ethernet cable (IEEE 802.3 100BASE-TX compliant cable or ANSI/TIA/EIA-568-B (Category 5)
compliant shielded 4-pair branched cable)
Line, star, or a combination of line and star
Slave station
RX
32 bits
RY
32 bits
RWr
32 words
RWw
32 words
Description
*1