Backup/restore

2.13.1 Outline

A backup/restore tool is available for backing up inverter parameters and the data used in the PLC function of inverter. The
backup data can be used to restore the data in the inverter. (Not compatible with safety parameters of the FR-E800-SCE)
This function is not supported depending on the date of manufacture of the inverter. For details of specification changes, refer
to
page
220.
 System configuration
Ethernet cable
Personal computer
(Backup/restore tool)

2.13.2 Initial setting for the backup/restore function

Use the following parameters to perform required settings for Ethernet communication between the inverter and other devices.
To make communication between other devices and the inverter, perform the initial settings of the inverter parameters to match
the communication specifications of the devices. Data communication cannot be made if the initial settings are not made or if
there is any setting error.
Pr.
Name
1427
Ethernet function selection
*1
1
N630
1428
Ethernet function selection
*1
2
N631
1429
Ethernet function selection
*1
3
N632
1430
Ethernet function selection
*1
4
N633
*1
The setting is applied after an inverter reset or next power-ON.
*2
The setting is available only for the FR-E800-EPA and the FR-E800-SCEPA.
*3
The setting is available only for the FR-E800-EPB and the FR-E800-SCEPB.
 Ethernet function selection (Pr.1427 to Pr.1430)
To use the backup/restore function, set "45237" (iQSS) in any of Pr.1427 to Pr.1430 Ethernet function selection 1 to 4. In
the initial status, Pr.1428 = "45237" (iQSS) and setting is not required. (Refer to
 Data to be backed up and restored
• The following data can be backed up and restored. The data other than those listed in the following table cannot be backed
up or restored.
Inverter parameters
Parameters used for activating the PLC function
Programs (including SFCs) used in the PLC function
Global device comment information used in the PLC function
Function block source information
 Backup/restore operation
• All inverter parameters and all data used in the PLC function of inverter can be backed up and restored.
• After restore operation, check the parameter setting values before starting operation.
Inverter
Initial
Setting range
value
5001
502, 5000 to 5002,
5006 to 5008, 5010 to
45237
5013, 9999, 34962
*2
44818
, 45237,
45238
45238, 47808
61450
9999
Item
*3
,
Set the application, protocol, and so on.
*2
,
page
173.)
Setting range
2. Ethernet Communication
2.13 Backup/restore
1
2
3
4
5
6
7
8
9
10
167

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E820s

Table of Contents