<Timing chart when writing to RAM>
*1
To the EEPROM, a writing is performed only once after the command Y100E turns ON.
*2
If the set data is changed at the command Y100E ON, the change is not applied to the inverter.
 Programming example for the fault record reading
The following program reads the fault records of the station 1 inverter to output to D1.
• Fault history No. 1 and 2 reading instruction code: H74 (hexadecimal)
For the error codes, refer to the Instruction Manual (Maintenance).
The reply code to the instruction code execution is set in D2. (Refer to
SM1536
SD1536.0 SD1540.0
(0)
M0
X20
(4)
M300
(8)
M301
X100F
(10)
M302
X100F
(17)
(25)
 Programming example for resetting the inverter at an inverter fault
The following program resets the station 1 inverter at an inverter fault.
SM1536
SD1536.0 SD1540.0
(0)
M0
X101A
X20
(4)
(8)
NOTE
• The inverter reset with the flag RY1A shown above is enabled at an inverter fault only.
• When Pr.349 Communication reset selection = "0", inverter reset is available independently of the operation mode.
• When using the instruction code execution request (RY0F) with the instruction code (HFD) and data (H9696) to reset the
inverter, set a value other than "0" in Pr.340 Communication startup mode selection or change the operation mode to the
Network operation mode. (For the program example, refer to
• Refer to
78
2. Ethernet Communication
2.6 CC-Link IE Field Network Basic
Y100D
W101
Inverter
running
frequency
page 217
for operation conditions of inverter reset.
<Timing chart when writing to EEPROM>
Y100E
*2
W101
Inverter
running
frequency
Reflect to the inverter when Y100E turns on
page
66.)
M0
PLS
M300
SET
M301
MOV
H74
W102
SET
Y100F
RST
M301
SET
M302
MOV
W3
D1
MOV
W2
D2
RST
Y100F
RST
M302
END
M0
Y101A
END
page
74.)
*1
Check the data link status of the station 1
Write error history No.1 and No.2 read
code (H74) to RWw2.
Turn on the instruction code execution request
(RY0F)
Read alarm data (RWr3) and reply code
(RWr2) to D1 and D2 when the instruction
code execution completion (RX0F) turns on.
Turn off the instruction code execution request
(RY0F)
Check the data link status of the station 1
Turn on the error reset request flag (RY1A)
Turn off the error reset request flag (RY1A)
when the error status flag (RX1A) is off.