Profinet Configuration; Initial Setting For Profinet - Mitsubishi Electric FR-E800 Instruction Manual (Communication

Hide thumbs Also See for FR-E800:
Table of Contents

Advertisement

([yyyymmdd]: revision date)
Mitsubishi Electric FA Global Website:
https://www.mitsubishielectric.co.jp/fa/download/software/detailsearch.do?mode=software&kisyu=/
inv&shiryoid=0000000041&lang=1&select=0&softid=1&infostatus=3_2_2&viewradio=1&viewstatus=01_0_0_010_20&viewpo
s=720_0
The download is free at the website above. For details, contact your sales representative.
NOTE
• The GSDML file is used in engineering software. To install the GSDML file properly, refer to the instruction manual of the
applicable engineering software.

2.12.2 PROFINET configuration

 Procedure
The procedure differs depending on the master device and the engineering software used. For details, refer to the Instruction
Manual of the master device and the engineering software.
 Before communication
1.
Connect each unit with an Ethernet cable. (Refer to
2.
Set "34962" (PROFINET) in any of Pr.1427 to Pr.1430 Ethernet function selection 1 to 4. (Refer to
(Example: Pr.1429 = "45238" (CC-Link IE TSN) (initial value) → "34962" (PROFINET))
When Pr.1429 = "45238 (initial value)" (CC-Link IE TSN), change the value to "34962" (PROFINET). When "45238"
is set in any of Pr.1427 to Pr.1430, the priority is given to CC-Link IE TSN, disabling PROFINET.
3.
Reset the inverter, or turn OFF and then ON the power.
 Network configuration
1.
Add the downloaded GSDML file to the engineering software.
2.
Detect the inverters on the network using the engineering software.
3.
Add the detected inverters to the network configuration settings.
4.
Configure the module settings for the inverters.
 Checking communication
The following table shows the status of the LEDs when communication is established between the programmable controller
and the inverter.
NS
Solid green
*1
The LED on either LINK1 or LINK2 will blink depending on the port (port 1 or 2) the Ethernet cable is connected to.

2.12.3 Initial setting for PROFINET

Use the following parameters to perform required settings for Ethernet communication between the inverter and other devices.
150
2. Ethernet Communication
2.12 PROFINET
MS
LINK1
Solid green
Blinking green
page
15.)
LINK2
*1
page
150.)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E820s

Table of Contents