• Set frequency: Speed setpoint A (NSOLL_A)
NSOLL_A = (5000 (50 Hz) × 16384 (4000h)) / 12000 (Pr.1 = 120 Hz) = 6826 (1AAAh)
Turning ON M0 starts operation at 50 Hz.
Turning OFF M0 stops operation.
 Setting example
• The following tables show example settings when user defined cyclic communication data are selected (Telegram 102).
When bit 10 of Control word 1 (STW1) is turned ON, data are written to the inverter. While bit 10 of Control word 1 (STW1)
is ON, the data is always updated. (The response time to write data is 100 ms at the most.)
• Telegram 102
Type
IO Data number
1
2
Setpoint Telegram
(master to slave)
3
4
1
2
3
Actual Value Telegram
4
(slave to master)
5
6
7
Name
Control word 1 (STW1)
Pr.1320
Pr.1321
Pr.1322
Status word 1 (ZSW1)
Pr.1330
Pr.1331
Pr.1332
Pr.1333
Pr.1334
Pr.1335
K6826