CHAPTER 5 FUNCTION ITEMS

5-2-22 Analog Output During Alarm

Switch between data having been output immediately before and a fixed value as an analog
output issued when measurement is disabled (with an alarm output) due to an excessive or
poor amount of light or deviation from the range. When the fixed value setting is selected,
either the maximum value (voltage output: +10.9V, current output: max. 29.5mA*) or
minimum value (voltage output: -10.9V, current output: 0mA) of the analog output is issued
upon an alarm.
* Varies with load impedance.
1. Display the input/output screen.
Touch
on the MENU Screen and display the input/
output screen.
2. Display the analog output screen.
Touch
analog output screen.
3. Display the analog output during alarm screen.
If
screen, the currently selected status is displayed. To change
the setting, touch the Select key. Select one of the following
settings:
Hold
4. Select the content of the fixed value.
If selecting a fixed value, it is possible to select output of the
maximum or minimum analog output during an alarm.
Fixed val: max.
5. Return to the MENU screen by touching
to the input/output screen by touching
Reference
Default Value: Hold
Supplementary Explanation
• Analog output is held without relation to the setting in the
timing input state (= upon alarm).
on the input/output screen and display the
is touched on the analog output
Fixed
val
Fixed val: min.
or return
.
5-31
MENU Screen
Input/output Screen
Analog Output Screen
Analog Output During Alarm Screen
Analog Output During Alarm Screen