Ga500 Branch Circuit Protection - YASKAWA V1000 Product Transition Manual

Industrial ac microdrive
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

4 Branch Circuit Protection

GA500 Branch Circuit Protection

Use branch circuit protection to protect against short circuits and to maintain compliance with UL61800-5-1. Yaskawa
recommends connecting semiconductor protection fuses on the input side for branch circuit protection.
• 240 V model fuse selection:
Use the fuses specified in this document or in the drive product instructions to prepare the drive for use on a circuit that
supplies not more than 31,000 Amps RMS and not more than 240 Vac when there is a short circuit in the power supply.
• 480 V model fuse selection:
Use the fuses specified in this document or in the drive product instructions to prepare the drive for use on a circuit that
supplies not more than 31,000 Amps RMS and not more than 480 Vac when there is a short circuit in the power supply.
The built-in short circuit protection of the drive does not provide branch circuit protection. The user must provide branch
circuit protection as specified by the National Electric Code (NEC), the Canadian Electric Code, Part I (CEC), and local
codes.
GA500 Catalog Code
GA50U_
B001
B002
B004
B006
B010
B012
B018
2001
2002
2004
2006
2010
2012
2021
2030
2042
2056
2070
2082
4001
4002
4004
4005
4007
4009
4012
4018
4023
10
Table 8 GA500 Branch Circuit Protection
Fuse Type: Class J, T, and CC Time-delay
Rated Current (A)
2
3.5
9
15
20
30
40
3
3.5
6
10
15
20
35
50
70
90
110
125
3
3.5
7
9
12
15
20
30
40
YASKAWA America, Inc. PL.GA500.01 YASKAWA AC Drive - V1000 to GA500 Transition Guide
Fuse Type: Semiconductor Fuse, Fast Acting
Single-Phase 240 V
FWH-25A14F
FWH-25A14F
Three-Phase 240 V
FWH-25A14F
FWH-25A14F
FWH-25A14F
FWH-25A14F
Three-Phase 480 V
(Manufacturer: EATON/Bussmann)
Model
FWH-60B
FWH-80B
FWH-100B
FWH-125B
FWH-150B
FWH-70B
FWH-70B
FWH-90B
FWH-100B
FWH-150B
FWH-200B
FWH-200B
FWH-225A
FWH-40B
FWH-40B
FWH-50B
FWH-70B
FWH-70B
FWH-90B
FWH-90B
FWH-80B
FWH-100B
Amp
25
25
60
80
100
125
150
25
25
25
25
70
70
90
100
150
200
200
225
40
40
50
70
70
90
90
80
100

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ga500Cimr-vu2001faaGa50u4004aba

Table of Contents