6 Control Circuit Wiring

Control Circuit Switches and Jumpers

Use this section to make any needed changes to the GA500 control circuit switches or jumpers.

V1000 Switches and Jumpers

Figure 8
DIP
Switch Function
Switch
Analog input signal selection for voltage or
S1
current for terminal A2
MEMOBUS/Modbus termination resistor
S2
switch setting for the RS-485, RS-422
communication terminals R-, R+, S-S+
Sinking/sourcing mode switch for digital
S3
input terminals S1~S7
26
DIP Switch S2
(in the ON position)
OFF
ON
Figure 8 V1000 DIP Switches
Table 12 V1000 DIP Switch Settings
Setting Value
V (left position)
I (right position) Current input (4 to 20 mA or 0 to 20 mA): default setting
YASKAWA America, Inc. PL.GA500.01 YASKAWA AC Drive - V1000 to GA500 Transition Guide
DIP Switch S1
V
DIP Switch S3
Voltage input (0 to 10 V)
ON
Internal termination resistor ON
Internal termination resistor OFF (no termination resistor): default
OFF
setting
SINK
Sinking Mode (0 V common): default setting
SOURCE
Sourcing Mode (+24 V common)
I
SINK
SOURCE
DIP Switch Setting Description