YASKAWA V1000 Product Transition Manual page 33

Industrial ac microdrive
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

Reg.
Param.
Name
No.
No.
Bi-Directional Speed
0x019E B3-14
Search Selection
Speed Search Method
0x01C0 B3-24
Selection
Timer Function On-
0x01A3 B4-01
Delay Time
Timer Function Off-
0x01A4 B4-02
Delay Time
0x01A5 B5-01
PID Function Setting
PID Sleep Function
0x01B3 B5-15
Start Level
0x01B5 B5-17
PID Accel/Decel Time
Dwell Reference at
0x01B6 B6-01
Start
Dwell Frequency at
0x01B8 B6-03
Stop
YASKAWA America, Inc. PL.GA500.01 YASKAWA AC Drive - V1000 to GA500 Transition Guide
Description
This parameter enables the drive to detect the
motor direction during speed search.
0: Disabled. Drive uses frequency reference
direction.
1: Enabled. Drive uses detected direction
This parameter is select of Speed search for start
or recovery of power failure.
1: Speed estimation type
2: Current detection type
Used in conjunction with a multi-function digital
input and a multi-function digital output
programmed for the timer function. This sets the
amount of time between when the digital input is
closed, and the digital output is enabled.
Used in conjunction with a multi-function digital
input and a multi-function digital output
programmed for the timer function. This sets the
amount of time the output remains enabled after
the digital input is opened.
This parameter determines the function of the
PID control.
0: Disabled
1: D = Feedback
2: D = Feed-Forward
3: Freq. Ref. + PID output (D = Feedback)
4: Freq. Ref. + PID output (D = Feed-Forward)
5: Same as Setting 1 w/ G7 Mode
6: Same as Setting 2 w/ G7 Mode
7: Same as Setting 3 w/ G7 Mode
8: Same as Setting 4 w/ G7 Mode
Sets the sleep function start frequency.
Note: Enabled even when PID control mode has
not been selected.
Applies an accel/decel time to the PID setpoint
reference. The drive's standard softstarter (C1-xx
and S-curve) still affects the output of the PID
algorithm.
The Dwell function is used to temporarily hold
the frequency when driving a motor with heavy
load.
Parameters b6-01 and b6-02 set the frequency to
hold and the time to maintain that frequency at
start.
Parameters b6-03 and b6-04 do the same at top.
The Dwell function is used to temporarily hold
the frequency when driving a motor with heavy
load.
Parameters b6-01 and b6-02 set the frequency to
hold and the time to maintain that frequency at
start.
Parameters b6-03 and b6-04 do the same at top.
7 Transfer of Parameter Settings
Setting Range
Initial Setting
GA500
V1000
GA500
A1-02
0~1
0~1
Depend
A1-02
1~2
0~1
Depend
0.0~3000.0 0.0~300.0
0.0
0.0~3000.0 0.0~300.0
0.0
0~8
0~4
0
A1-02
0.0~590.0
0.0~400.0
Depend
(all 0.0)
0.0~6000.0 0~255
0.0
A1-02
0.0~590.0
0.0~400.0
Depend
(all 0.0)
A1-02
0.0~590.0
0.0~400.0
Depend
(all 0.0)
Base Unit
V1000
DEC
0
DEC
0
DEC sec
0.0
DEC sec
0.0
DEC
0
DEC Hz
0.0
DEC sec
0.0
DEC Hz
0.0
DEC Hz
0.0
33