Description
3.4 Three-phase devices 80 A
3.4
Three-phase devices 80 A
①
②
③
④
⑤
⑥
28
Sealing cover
Energy flow indicator
•
If the device detects an active energy flow, a rotating symbol appears on the top right of the
display.
•
If no active energy consumption is present, or if the load is drawing less than the starting
current, the rotating symbol disappears.
•
If energy measurement (export) is activated (P01.02 = ON) and if the device detects an
active energy flow, a counter-clockwise rotating symbol appears on the top right of the dis-
play.
•
If measurement of the active energy (export) is deactivated (P01.02 = OFF) and if one or
more phases has been connected incorrectly, error code Err 3 appears on the display.
Check the connections.
"Increase" key
"Decrease" key
"Next" key
Active energy pulse indicator
The red LED on the front panel outputs 1000 pulses for every kWh of energy consumed or out-
put. If energy is imported from at least one of the phases, the LED indicates the energy as a
balance between imported and exported energy. The LED pulse frequency is proportional to the
energy.
You will find information on operation in chapter Keypad functions
(Page 29) ff.
7KT16 energy meter
Equipment Manual, 09/2020, 2514284147-04