Three-Phase Connection (3P4W) - Siemens SENTRON 7KM PAC2200 Product Manual

Power monitoring device
Hide thumbs Also See for SENTRON 7KM PAC2200:
Table of Contents

Advertisement

2.5.3.1

Three-phase connection (3P4W)

The measurement data is presented on three pages (Mapping 0) and on four pages
(Mapping 1). Multipage-capable masters can read out all three or four pages.
As an example, the coding of the data record with ID 13 (connection type 3P4W, Mapping 1,
i.e. version 32) is more accurately explained in the RSP_UD2 response datagram (see also
M-BUS specification):
Measured variable ID 13: L2 active energy export tariff 2
BYTE No.
Byte 1
Byte 2
Byte 3
Byte 4
Bytes 5-6
Bytes 7-12
All measurement data that can be read out via the M-BUS are listed in the following table.
ID
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
PAC2200
Equipment Manual, 12/2019, L1V30415167B-03
Coding
0x86
0x20
0x83
0xBC
0xFC 0x02
XX XX XX XX XX XX
Measured variable
Secondary total active energy (MID register)
Total active energy import tariff 1
Total active energy import tariff 2
Total active energy export tariff 1
Total active energy export tariff 2
L1 active energy import tariff 1
L1 active energy import tariff 2
L1 active energy export tariff 1
L1 active energy export tariff 2
L2 active energy import tariff 1
L2 active energy import tariff 2
L2 active energy export tariff 1
L2 active energy export tariff 2
L3 active energy import tariff 1
L3 active energy import tariff 2
L3 active energy export tariff 1
L3 active energy export tariff 2
Total active power
Active power L1
Active power L2
Active power L3
Voltage L1-N
Voltage L2-N
Voltage L3-N
Description
DIF value format INT48 -> Integer 6 bytes length
DIFE tariff 2
VIF active energy / unit Wh
VIFE export
VIFE phase L2
Integer value of measured variable
Length
(bits)
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
32
32
32
32
32
32
32
Description
2.5 Communication
Format
Unit
INT48
Wh
INT48
Wh
INT48
Wh
INT48
Wh
INT48
Wh
INT48
Wh
INT48
Wh
INT48
Wh
INT48
Wh
INT48
Wh
INT48
Wh
INT48
Wh
INT48
Wh
INT48
Wh
INT48
Wh
INT48
Wh
INT48
Wh
FLOAT32
W
FLOAT32
W
FLOAT32
W
FLOAT32
W
FLOAT32
V
FLOAT32
V
FLOAT32
V
29

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents