For the variant with M-Bus interface
Code
P8-01
P8-02
P8-03
P8-04
Explanations about the code
P1-01
P1-02
P2-01
P2-02
P2-03
P3-01,
P3-02,
P3-03
P4-01,
P4-02,
P4-03
7KT16 energy meter
Equipment Manual, 09/2020, 2514284147-04
Description
Primary address
Secondary address HIGH
Secondary address LOW
Baud rate
Setting 0000 (default) deactivates password protection. Every other setting defines
the password for access to advanced functions.
Activate energy displays (export)
Select code for comparison with threshold values for hour counter 1. You can find
more information in Settable values for parameters P2.01, P3.01, P4.01 (Page 40).
Threshold for activation of hour counter 1. Note: The measurements are updated
every second.
Threshold for deactivation of hour counter 1. The measurements are updated every
second.
• P2-02 ≥ P2-03:
– The hour counter is activated if the value defined by P2-01 is higher than
P2-02.
– The hour counter is deactivated if its value is lower than P2-03 (maximum
limit with hysteresis).
• P2-02 < P2-03:
– The hour counter is activated if the value defined by P2-01 is lower than
P2-02.
– The hour counter is deactivated if its value is higher than P2-03 (minimum
limit with hysteresis).
As with P2-01, P2-02 and P2-03, with reference to hour counter 2.
As with P2-01, P2-02 and P2-03, with reference to hour counter 3.
3.4 Three-phase devices 80 A
Default
Range
001
001 ... 250
Serial
0000 ... 9999
number
Serial
0000 ... 9999
number
2400
•
300
•
600
•
1200
•
2400
•
4800
•
9600
•
19200
•
38400
Description
35