Modbus Address Table For Three-Phase Devices 80 A With Modbus Interface - Siemens SENTRON 7KT PAC1600 Equipment Manual

Energy meter
Hide thumbs Also See for SENTRON 7KT PAC1600:
Table of Contents

Advertisement

6.4.3

Modbus address table for three-phase devices 80 A with Modbus interface

Continuous measured values
Modbus measured variables with the function codes 03 and 04
Address
Number
of regis-
Hex
Decimal
ters
0002
2
2
0004
4
2
0006
6
2
0008
8
2
000A
10
2
000C
12
2
000E
14
2
0010
16
2
0012
18
2
0014
20
2
0016
22
2
0018
24
2
001A
26
2
001C
28
2
001E
30
2
0020
32
2
0022
34
2
0024
36
2
0026
38
2
0028
40
2
002A
42
2
002C
44
2
002E
46
2
0030
48
2
0032
50
2
0034
52
2
0036
54
2
0038
56
2
003A
58
2
003C
60
2
003E
62
2
0040
64
2
7KT16 energy meter
Equipment Manual, 09/2020, 2514284147-04
Format
Access
Unit
UINT32
R
V
UINT32
R
V
UINT32
R
V
UINT32
R
A
UINT32
R
A
UINT32
R
A
UINT32
R
V
UINT32
R
V
UINT32
R
V
INT32
R
W
INT32
R
W
INT32
R
W
INT32
R
var
INT32
R
var
INT32
R
var
UINT32
R
VA
UINT32
R
VA
UINT32
R
VA
INT32
R
INT32
R
INT32
R
UINT32
R
Hz
UINT32
R
V
UINT32
R
V
INT32
R
W
INT32
R
var
UINT32
R
VA
INT32
R
6.4 Modbus address register
Factor
Measured variable
0.01
Voltage L1N
0.01
Voltage L2N
0.01
Voltage L3N
0.0001
Current L1
0.0001
Current L2
0.0001
Current L3
0.01
Voltage L1L2
0.01
Voltage L2L3
0.01
Voltage L3L1
0.01
Active power L1
0.01
Active power L2
0.01
Active power L3
0.01
Reactive power L1
0.01
Reactive power L2
0.01
Reactive power L3
0.01
Apparent power L1
0.01
Apparent power L2
0.01
Apparent power L3
0.0001
Power factor L1
0.0001
Power factor L2
0.0001
Power factor L3
0.01
Frequency
0.01
Average Voltage LN
0.01
Average Voltage LL
0.01
Average Active power
0.01
Average Reactive power
0.01
Average Apparent power
0.0001
Average Power factor
Commissioning
91