Installing an S7-200 Micro PLC or Expansion Module onto a Standard Rail

Warning
!
Attempts to install or remove S7-200 CPUs or related equipment when they are
powered up could cause electric shock or faulty operation of equipment.
Failure to disable all power to the S7-200 CPUs and related equipment during
installation or removal procedures may result in death or serious personal injury,
and/or damage to equipment.
Always follow appropriate safety precautions and ensure that power to the S7-200
is disabled before attempting to install or remove S7-200 CPUs or related
equipment.
To install the S7-200 CPU onto a standard rail, follow these steps:
1.
Secure the rail to the mounting panel every 75 mm (3.0 in.).
2.
Snap open the clip (located on the bottom of the S7-200) and hook the back of
the S7-200 onto the rail.
3.
Snap the clip closed, carefully checking to ensure that the clip has fastened
the S7-200 securely onto the rail.
To install the expansion module onto a standard rail, use the following steps:
1.
Snap open the clip and hook the back of the expansion module onto the rail
next to the CPU or expansion module.
2.
Snap the clip closed to secure the expansion module to the rail. Carefully
check to ensure that the clip has fastened the module securely onto the rail.
3.
Plug the expansion module ribbon cable into the CPU connector under the
front access door. The cable is keyed for correct orientation.
4.
Installation is complete.
Note
Modules in an environment with high vibration potential or modules that have been
installed in a vertical position may require DIN rail stops.
S7-200 Programmable Controller System Manual
A5E00066097-02
Installing an S7-200 PLC