Configuration - ICP DAS USA MDC-700 Series User Manual

Hide thumbs Also See for MDC-700 Series:
Table of Contents

Advertisement

2. Configuration   
The necessary configuration for Modbus TCP communication, Modbus RTU communication and 
polling definition is handled by a single file named "config.csv". Just follow the easy‐to‐use format 
defined in the config.csv file and import the new config.csv file via a simple mouse‐click on the main 
page of the MDC‐700, the data on those Modbus RTU slave devices can be accessed over an 
Ethernet.   
 
Only the Function code 01/02/03/04 can be used in the config.csv file:     
01: Read Coil Status (Read DO) 
02: Read Input Status (Read DI) 
03: Read Holding Registers (Read AO) 
04: Read Input Registers (Read AI) 
 
If you would like to write data to a digital or analog output channel on a Modbus RTU slave device, 
the output channel needs be mapped with a local register address in the MDC‐700 by editing the 
polling definition with using corresponding read function code (01 or 03). Refer to Q4 in the 4. FAQ 
section for more detailed information. 
 
 
The following section will help you to set up your MDC‐700 module, and show you how to use the 
web interface to obtain configuration and other information related to the MDC module and 
associated slave devices. 
 
Basic operating procedure 
    Step 1: Assign a valid IP address to the MDC‐700. 
    Step 2: Edit the config.csv file.   
Note that before editing this file, you should confirm the parameter value for any 
associated Slave devices. 
    Step 3: Upload the config.csv file to the MDC module. 
    Step 4: Verify the status of both the connection and the configuration by browsing the web. 
Copyright © 2014 ICP DAS Co., Ltd. All Rights Reserved.  ∗  E‐mail: service@icpdas.com                                          ‐ 13 ‐ 
 