Situation #2: ERROR: ILLEGAL DATA ADDRESS. The address settings are not allowable addresses for 
the slave.     
Solution: Check and fix the RegStartAddr and RegCount settings.
UseComPort SlaveModbusID FunctionCode RegStartAddr RegCount
 
 
 
Situation #3: ERROR appeared only. The slave device is abnormal, you have to check the responses 
from the device. 
Solution: 
Step 1: Power cycle the slave device. 
Step 2: Use third‐party communication software to get the error code responded by the slave 
device, and follow the instructions in the user manual for the device to solve the problem. 