Faq; Q1: What Are The Maximum Numbers Of Polling Definition And Local Register; Q2: What Is The Maximum Number Of Registers Can Be Accessed In One Modbus Command - ICP DAS USA MDC-700 Series User Manual

Hide thumbs Also See for MDC-700 Series:
Table of Contents

Advertisement

4. FAQ
Q1: What are the maximum numbers of polling definition and local register?
A1: The maximum number of polling definition in a MDC‐700 is 240, each definition can access up 
to 64 registers. Each of the four tables (DI/DO/AI/DO) can store up to 9600 registers for polled 
data. 
Q2: What is the maximum number of registers can be accessed in one Modbus 
command from a Modbus master device?
A2: By following the Modbus protocol, the maximum amount of registers that one command can 
access is 255 of function code 01 and 02, and 126 of function code 03 and 04. 
 
Copyright © 2014 ICP DAS Co., Ltd. All Rights Reserved.  ∗  E‐mail: service@icpdas.com                                          ‐ 29 ‐ 

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mdc-711Mdc-714Mdc-741Mdc-714 crMdc-711 crMdc-741 cr

Table of Contents