Power Connector 
         
 
 
 
 
 
 
 
 
 
 
 
 
Configuration Display 
        MDC‐700 includes a 5‐digit 7‐Segment LED display to indicate configuration in a module as 
below:   
 
 
  11111. 
 
  1. 192 
 
  2. 168 
 
  3. 255 
 
  4.      1 
 
  22222. 
 
      502 
 
      001 
 
 
  33333. 
 
  1.1152 
 
  2.1152 
 
 
  44444. 
 
  1. 801 
 
  2. 801 
 
  55555. 
 
        00 
 
 
 
Copyright © 2014 ICP DAS Co., Ltd. All Rights Reserved.  ∗  E‐mail: service@icpdas.com                                          ‐ 10 ‐ 
The IP address for the MDC‐700 
    (192.168.255.1) 
Modbus TCP communication settings 
    Port: 502 
    Net ID: 1 
Baud rate setting for each COM port 
    COM1: 115200 bps 
    COM2: 115200 bps
Data format setting for each COM port 
    COM1: 8N1 
    COM2: 8N1 
The count of TCP/IP connection 
    0: No TCP/IP connection 