29. Wire Distance Chart
To meet NEC compliance (North America), the largest PV array that can be connected to a FLEXmax 80
must have a rated short-circuit current of 64 amps or less and 48 amps or less for a FLEXmax 60. The
following charts show the maximum distance of various gauge two-conductor copper wire from the
PV array to the Charge Controller with a 1.5% maximum voltage drop. Temperature and conduit fi ll cor-
rections may be required. Using a higher voltage PV array with a low voltage battery system allows you
to use a much smaller wire size or go up to 5 times as far with the same gauge wire.
FLEXmax 60 and FLEXmax 80
and allow for a 1.5% voltage drop)
12V PV ARRAY (16v Vmp)
#8
WIRE GAUGE
10
15
20
8
30
5
40
4
50
3
60
3
70
2
80
2
24V PV ARRAY (32v Vmp)
#8
WIRE GAUGE
10
31
20
15
30
10
40
8
50
6
60
5
70
4
80
4
36V PV ARRAY (48v Vmp)
#8
WIRE GAUGE
10
46
20
23
30
15
40
12
50
9
60
8
70
7
80
6
NOTE: Numbers in bold might not meet NEC requirements
78
(The fi gures below assume THWN 75
#6
#4
#3
24
39
49
12
19
24
8
13
16
6
10
12
5
8
10
4
6
8
3
6
7
3
5
6
#6
#4
#3
49
78
98
24
39
49
16
26
33
12
19
24
10
16
20
8
13
16
7
11
14
6
10
12
#6
#4
#3
73
117
147
37
58
73
24
39
49
18
29
37
15
23
29
12
19
24
10
17
21
9
15
18
0
C two-conductor copper wire
#2
#1
#1/0
62
78
98
31
39
49
21
26
33
15
19
25
12
16
20
10
13
16
9
11
14
8
10
12
#2
#1
#1/0
124
156
197
62
78
98
41
52
66
31
39
49
25
31
39
21
26
33
18
22
28
15
19
25
#2
#1
#1/0
186
234
295
93
117
148
62
78
98
46
58
74
37
47
59
31
39
49
27
33
42
23
29
37
#2/0
#3/0
#4/0
124
157
197
62
78
99
41
52
66
31
39
49
25
31
39
21
26
33
18
22
28
16
20
25
#2/0
#3/0
#4/0
248
313
395
124
157
197
83
104
132
62
78
99
50
63
79
41
52
66
35
45
56
31
39
49
#2/0
#3/0
#4/0
372
470
592
186
235
296
124
157
197
93
117
148
74
94
118
62
78
99
53
67
85
47
59
74
METRIC
2
#8...8.37mm
2
#6...13.30mm
#4...21.15mm
2
2
#3...26.7mm
#2...33.6mm
2
2
#1/0...53.5mm
2
#2/0...67.4mm
#4/0...107mm
2