LOW BATTERY DISCONNECT
AUX MODE
Low Batt Disconnect
Output: On
EXIT NEXT SET MODE
AUX MODE
Low Batt Disconnect
EXIT
Delay Time Sec
BACK
-
38
On
TIME VOLT
01
Timer
001
+
When the battery voltage falls below the disconnect
volts, the AUX connected loads only are disconnected;
the AUX connected loads only are connected when
On
the battery voltage rises above the reconnect volts.
To adjust these set points, press the <TIME> and
Off
<VOLT> soft keys.
Auto
Press the <TIME> and <VOLT> soft keys to adjust the
set points.
Press either the < - > or < + > soft key to adjust
the delay time. This is the time period the Charge
Controller waits before either activating or deactivating
the AUX MODE when either the disconnect or
reconnect voltages are reached. When the low voltage
occurs, the timer shows the seconds remaining before
disconnecting. When the reconnect voltage is reached,
the timer shows the user-determined time before
connecting. Press the <BACK> soft key to return to the
Low Batt Disconnect screen.