NOTE: Input conductors and circuit breakers must be rated at 1.56 times the short-circuit current of
the PV array. OutBack 100% duty continuous breakers only need to be rated at 1.25 times the short-
circuit current.
• Please see the wire Distance Chart and complete Wire and Disconnect Sizing on pages 78-81 for
other suitable conductor/wire sizing.