Cross-sectional areas -Tightening torques

Recommended cross-sectional area to DINVDE 0276-1000 and DINVDE 0100-
540 (PE) trefoil arrangement.
Recommended cross-sectional areas for AC-connection.
Unit type
400 V / 500 V / 525 V
DCS800-A01-0020-04/05-D
DCS800-A02-0025-04/05-D
DCS800-A01-0045-04/05-D
DCS800-A02-0050-04/05-D
DCS800-A01-0065-04/05-D
DCS800-A02-0075-04/05-D
DCS800-A01-0125-04/05-D
DCS800-A02-0140-04/05-D
DCS800-A01-0230-04/05-D
DCS800-A02-0260-04/05-D
DCS800-A01-0315-04/05-D
DCS800-A02-0350-04/05-D
DCS800-A01-0470-04/05-D
DCS800-A02-0520-04/05-D
DCS800-A01-0610-04/05-D
DCS800-A02-0680-04/05-D
DCS800-A01-0740-04/05-D
DCS800-A02-0820-04/05-D
DCS800-A01-0900-04/05-D
DCS800-A02-1000-04/05-D
DCS800-A0x-1200-04/05-D
DCS800-A0x-1200T-04/05-D
DCS800-A0x-1500-04/05-D
DCS800-A0x-2000-04/05-D
DCS800-A0x-2050-05-D
DCS800-A0x-2500-04/05-D
DCS800-A0x-3000-04/05-D
DCS800-A0x-3300-04/05-D
DCS800-A0x-4000-04/05-D
DCS800-A0x-5200-04/05-D
DCS800-A0x-6600-04/05PD
DCS800-A0x-8000-04/05PD
DCS800-A0x-10400-04/05PD
600 V / 690 V
DCS800-A01-0290-06-D
DCS800-A02-0320-06-D
DCS800-A01-0590-06-D
DCS800-A02-0650-06-D
DCS800-A0x-0900-06/07-D
DCS800-A0x-1500-06/07-D
DCS800-A01-2000-06/07-D
DCS800-A0x-2050-06/07-D
DCS800-A0x-2500-06/07-D
DCS800-A0x-3000-06/07-D
DCS800-A0x-3300-06/07-D
DCS800-A0x-4000-06/07-D
DCS800-A0x-4800-06/07-D
DCS800-A0x-6600-06/07PD
DCS800-A0x-8000-06/07PD
DCS800-A0x-9600-06/07PD
Electrical Installation
Amount of single
Amount of holes per phase for
cores and cross -
sectional area
Group drives are connected via
connected per
phase / PE (1*)
For sizes D1 - D3 terminals are
IAC [A~]
[mm²]
15
1 * 6²
18
1 * 6²
33
1 * 10²
37
1 * 10²
49
1 * 16²
55
1 * 16²
94
1 * 35²
103
1 * 35²
164
1 * 95²
189
1 * 95²
234
1 * 120²
246
1 * 120²
328
1 * 185²
369
1 * 185²
443
2 * 150²
492
2 * 150²
558
2 * 185²
615
2 * 185²
664
2 * 240²
738
2 * 240²
935
4 * 150²
935
4 * 150²
1169
4 * 185²
1517
6 * 150²
1599
6 * 185²
2009
8 * 185²
2460
10 * 185²
2706
10 * 185²
3280
10 * 240²
4182
14 * 240²
5084
2 x 10 * 185²
6232
2 x 10 * 240²
8036
2 x 14 * 240²
180
1 * 95²
197
1 * 120²
303
2 * 150²
328
2 * 150²
701
4 * 95²
1169
4 * 185²
1517
6 * 150²
1599
6 * 185²
2009
8 * 185²
2460
10 * 185²
2706
10 * 185²
3280
10 * 240²
3854
12 * 240²
5084
2 x 10 * 185²
6232
2 x 10 * 240²
7380
2 x 12 * 240²
3ADW000352R0101 DCS800-A Installation Manual e a
AC - connection (U, V, W) + PE
Size of
single drives;
screws (2*);
Not for UL
incoming supply units;
used
1 terminal (16-95 mm²)
1 terminal (16-95 mm²)
1 terminal (16-95 mm²)
1 terminal (16-95 mm²)
1 terminal (16-95 mm²)
1 terminal (16-95 mm²)
1 terminal (16-95 mm²)
1 terminal (16-95 mm²)
1 terminal (16-95 mm²)
1 terminal (16-95 mm²)
1 terminal (16-95 mm²)
1 terminal (16-95 mm²)
2
2
2
2
2
2
2
2
4
4
4
4
8
8
12
16
16
16
1 terminal (16-95 mm²)
1 terminal (16-95 mm²)
2
2
4
4
4
8
8
12
16
16
16
UL as per Nema 2 (3*):
Amount of holes per phase for
single drives;
Group drives are connected via
incoming supply units;
For sizes D1 - D3 terminals are
used
1 terminal (16-95 mm²)
1 terminal (16-95 mm²)
1 terminal (16-95 mm²)
1 terminal (16-95 mm²)
1 terminal (16-95 mm²)
1 terminal (16-95 mm²)
1 terminal (16-95 mm²)
1 terminal (16-95 mm²)
1 terminal (16-95 mm²)
1 terminal (16-95 mm²)
1 terminal (16-95 mm²)
1 terminal (16-95 mm²)
M12
2
M12
2
M12
4
M12
4
M12
4
M12
4
M12
4
M12
4
M12
M12
M12
M12
M12
M12
M12
M12
M12
M12
1 terminal (16-95 mm²)
1 terminal (16-95 mm²)
M12
2
M12
2
M12
M12
M12
M12
M12
M12
M12
M12
M12
Size
D1
D2
D3
D4
D5
D5
D6
D7
D7P
D7P
D3
D4
D5
D5
D6
D7
D7P
D7P