50
Recommended cross-sectional areas for DC-connection
Unit type
DC I [A-]
400 V / 500 V / 525 V
DCS800-A01-0020-04/05-D
DCS800-A02-0025-04/05-D
DCS800-A01-0045-04/05-D
DCS800-A02-0050-04/05-D
DCS800-A01-0065-04/05-D
DCS800-A02-0075-04/05-D
DCS800-A01-0125-04/05-D
DCS800-A02-0140-04/05-D
DCS800-A01-0230-04/05-D
DCS800-A02-0260-04/05-D
DCS800-A01-0315-04/05-D
DCS800-A02-0350-04/05-D
DCS800-A01-0470-04/05-D
DCS800-A02-0520-04/05-D
DCS800-A01-0610-04/05-D
DCS800-A02-0680-04/05-D
DCS800-A01-0740-04/05-D
DCS800-A02-0820-04/05-D
DCS800-A01-0900-04/05-D
DCS800-A02-1000-04/05-D
DCS800-A0x-1200-04/05-D
DCS800-A0x-1200T-04/05-D
DCS800-A0x-1500-04/05-D
DCS800-A0x-2000-04/05-D
DCS800-A0x-2050-05-D
DCS800-A0x-2500-04/05-D
DCS800-A0x-3000-04/05-D
DCS800-A0x-3300-04/05-D
DCS800-A0x-4000-04/05-D
DCS800-A0x-5200-04/05-D
DCS800-A0x-6600-04/05PD
DCS800-A0x-8000-04/05PD
DCS800-A0x-10400-04/05PD
600 V / 690 V
DCS800-A01-0290-06-D
DCS800-A02-0320-06-D
DCS800-A01-0590-06-D
DCS800-A02-0650-06-D
DCS800-A0x-0900-06/07-D
DCS800-A0x-1500-06/07-D
DCS800-A01-2000-06/07-D
DCS800-A0x-2050-06/07-D
DCS800-A0x-2500-06/07-D
DCS800-A0x-3000-06/07-D
DCS800-A0x-3300-06/07-D
DCS800-A0x-4000-06/07-D
DCS800-A0x-4800-06/07-D
DCS800-A0x-6600-06/07PD
DCS800-A0x-8000-06/07PD
DCS800-A0x-9600-06/07PD
Electrical Installation
With DC - fuses
Amount of single
Amount of
cores and cross -
holes for
sectional area
connection
connected per
per phase
phase / PE (1*)
[mm²]
18
1 * 6²
2
22
1 * 6²
2
40
1 * 10²
2
45
1 * 10²
2
60
1 * 16²
2
67
1 * 16²
2
115
1 * 35²
2
125
1 * 35²
2
200
1 * 95²
2
230
1 * 95²
2
285
1 * 120²
2
300
1 * 120²
2
400
1 * 185²
2
450
1 * 185²
2
540
2 * 150²
2
600
2 * 150²
2
680
2 * 185²
2
750
2 * 185²
2
810
2 * 240²
2
900
2 * 240²
2
1140
4 * 150²
1140
4 * 150²
1425
5 * 185²
1850
6 * 185²
1950
7 * 185²
2450
8 * 185²
3000
11 * 185²
3300
11 * 185²
4000
12 * 240²
5100
15 * 240²
6200
2 x 11 * 185²
7600
2 x 12 * 240²
9800
2 x 15 * 240²
220
1 * 95²
2
240
1 * 95²
2
370
1 * 185²
2
400
1 * 185²
2
855
4 * 95²
1425
5 * 185²
1850
6 * 185²
1950
7 * 185²
2450
8 * 185²
3000
11 * 185²
3300
11 * 185²
4000
12 * 240²
4700
14 * 240²
6200
2 x 11 * 185²
7600
2 x 12 * 240²
9000
2 x 14 * 240²
3ADW000352R0101 DCS800-A Installation Manual e a
DC - connection (U+, U-) + 2 * PE
Size of
Amount of holes for
screws (2*)
connection per phase;
For size D1 - D3 terminals
are used
M10
1 terminal (16-95 mm²)
M10
1 terminal (16-95 mm²)
M10
1 terminal (16-95 mm²)
M10
1 terminal (16-95 mm²)
M10
1 terminal (16-95 mm²)
M10
1 terminal (16-95 mm²)
M10
1 terminal (16-95 mm²)
M10
1 terminal (16-95 mm²)
M10
1 terminal (16-95 mm²)
M10
1 terminal (16-95 mm²)
M10
1 terminal (16-95 mm²)
M10
1 terminal (16-95 mm²)
M10
2
M10
2
M10
4
M10
4
M10
4
M10
4
M10
4
M10
4
8
8
8
8
8
8
8
16
16
16
M10
1 terminal (16-95mm²)
M10
1 terminal (16-95mm²)
M10
4
M10
4
8
8
8
8
8
8
16
16
16
Without DC - fuses
Size of
UL as per Nema 2 (3*):
screws (2*);
Amount of holes per
Not for UL
phase for single drives;
For size D1 - D3
terminals are used
1 terminal (16-95 mm²)
1 terminal (16-95 mm²)
1 terminal (16-95 mm²)
1 terminal (16-95 mm²)
1 terminal (16-95 mm²)
1 terminal (16-95 mm²)
1 terminal (16-95 mm²)
1 terminal (16-95 mm²)
1 terminal (16-95 mm²)
1 terminal (16-95 mm²)
1 terminal (16-95 mm²)
1 terminal (16-95 mm²)
M12
2
M12
2
M12
4
M12
4
M12
4
M12
4
M12
4
M12
4
M12
8
M12
8
M12
8
M12
8
M12
M12
M12
M12
M12
M12
1 terminal (16-95mm²)
1 terminal (16-95mm²)
M12
4
M12
4
M12
8
M12
8
M12
8
M12
M12
M12
M12
M12
M12
Size
D1
D2
D3
D4
D5
D6
D6
D7
D7P
D7P
D3
D4
D5
D6
D6
D7
D7P
D7P