Air Duct Outlet for Enclosed Converters with D6 / D7 Modules

Air
ventilation
hood
(option)
Cabinet
D6/D7
module
Air duct for D6 / D7 module

Air baffle plates

To keep the converter module as cool as possible cooling air re-circulation outside
and inside the cabinet has to be prevented.
To prevent outside cooling air re-circulation external measures have to made.
To prevent inside cooling air re-circulation air baffle plates are used:
Main air flow in
Air baffle plates
Mechanical Installation
Air duct outlet
Air duct
Air
with
Wall
Main air flow out
Hot
Air baffle plates
COOL AREA
prev recirc.dsf
3ADW000352R0101 DCS800-A Installation Manual e a
Converter modules size D6 / D7 installed in
cabinets DCS800-A produce a considerable
amount of power loss to be removed by air
cooling. In most cases the switch room is not
capable to absorb the heated air. That is why
cabinets with converter modules sizes D6 / D7
are provided with an adapter for connection to an
air duct (air duct to be supplied for by customer).
In case there is no air duct, the option Air
Ventilation Hood is required to meet protection
class IP 21.
This option can also be used for connection to an
existing air duct outlet (solution indicated by
dashed lines).