ABB DCS800 Series Installation Manual page 58

Enclosed converter
Hide thumbs Also See for DCS800 Series:
Table of Contents

Advertisement

58
Stripped cable
Cable screen
5. Lock the two parts of the lead-through plate by tightening the positioning
screws.
6. Top entry: If more than one cable go through a single grommet, the grommet
must be sealed by Loctite 5221 (catalogue number 25551).
Top entry
Electrical Installation
Conductive surface of the
screen exposed
Cut the screen at the midpoint of the bare part. Be careful not to cut
the conductors.
Turn the screen inside out to expose its conductive surface.
Cover the turned screen and the stripped cable with copper foil to
keep the shielding continuous.
Note:
The ground wire (if present) must not be cut.
Push the two parts of the lead-through plate together so that the
conductive cushions press tightly round the foil covered screen.
Side view
3ADW000352R0101 DCS800-A Installation Manual e a
Stripped part covered with
copper foil

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dcs800-a

Table of Contents