The connections L+, L-, F+ and F- at motor and drive are OK.
The control connections are OK.
If pulse encoder is used, check the encoder cables and correct direction of rotation, see
DCS800 Hardware Manual (3ADW000194).
PT 100, PTC, Klixon cables: Check that the connections are appropriate for the type of sensor
used in the motor.
Check the prevention of unexpected start-up (on inhibit, coast stop) cables.
Check the emergency stop cables.
For all external cables make sure that both ends of the cables are connected and the cables do
not cause any damage or danger when power is being switched on.
Cleanliness of the cabinets and surroundings, e.g.:
o there are no tools or other foreign objects inside the cabinets or waste left from
installation e.g. cable trimmings,
o there is no garbage under the cabinets (the cooling air fan will draw the garbage inside
the cabinets),
o use a vacuum cleaner to remove any dirt. Do not use compressed air!
Before start-up close all doors, covers, air baffle plates and check that the finger protection
covers are mounted properly.