Replacing A Cabinet Rpdu - Huawei FusionModule 1000B Maintenance Manual

Air-cooled it solution
Table of Contents

Advertisement

FusionModule1000B Air-Cooled IT Solution
Maintenance Guide
Preparations
Tools: Phillips screwdriver, protective gloves
Materials: spare monitoring rPDU
Documents: none
Skill requirement: electrician's work permit
Procedure
Step 1 Shut down devices powered by the monitoring rPDU.
Step 2 Switch off the rPDU circuit breaker, and unplug devices powered by the rPDU.
Step 3 Remove the monitoring rPDU using a Phillips screwdriver.
Figure 6-5 Removing screws
Step 4 Replace the monitoring rPDU, connect the industrial connectors, and bind the cables using
cable ties.
Step 5 Check that the new rPDU is working properly.
Step 6 Insert device power plugs in the rPDU.
Step 7 Restart devices shut down in
----End
Follow-up Procedure
Dispose of the removed rPDU that is confirmed faulty.

6.1.6 Replacing a Cabinet rPDU

Prerequisites
Issue 02 (2017-01-10)
An rPDU needs to be replaced.
A spare rPDU of the same model is available and functional.